Black Box Explains...10-GbE, CAT6A, and ANEXT.

The IEEE released the 802.3an 10GBASE-T standard in June 2006. This standard specifies 10-Gbps data transmission over four-pair copper cabling. 10-Gigabit Ethernet (10-GbE) transmission includes up to 37 meters of... more/see it nowCAT6 cable (with installation mitigation techniques), 100 meters of Augmented Category 6 (CAT6A) UTP or F/UTP cable or 100 meters of S/FTP CAT7/Class F cable.

CAT6A is the ANSI/TIA 10-Gigabit Ethernet (10-GbE) over copper standard. Its requirements are covered in ANSI/TIA-568-C.2 (Balanced Twisted-Pair Communications Cabling and Components Standard) published in August 2009. It defines 10-Gigabit data transmission over a 4-connector twisted-pair CAT6A copper cable for a distance of 100 meters.

Category 6A cabling is designed to support next-generation applications, including the transfer of large amounts of data at high speeds, up to 10 Gbps. CAT6A extends electrical specifications to 500 MHz from 250 MHz for CAT6 cabling. CAT6A cables are fully backward compatible with previous categories, including CAT6 and 5e. Category 6A is also designed to support bundled cable installations up to 100 meters and PoE+ low-power implementations. The standard includes the performance parameter, Alien Crosstalk (ANEXT). Because of its higher performance transmission speeds and higher MHz rating, CAT6A cable needs to be tested for external noise outside the cable, which wasn’t a concern with previous cabling categories. CAT6A UTP also has a much larger diameter than previous cables.

Alien crosstalk (ANEXT) is a critical and unique measurement in 10-GbE systems. Crosstalk, measured in 10/100/1000BASE-T systems, is the mixing of signals between wire pairs within a cable. Alien Crosstalk, in 10-GbE systems, is the measurement of the unwanted signal coupling between wire pairs in different and adjacent cables or from one balanced twisted-pair component, channel, or permanent link to another.

The amount of ANEXT depends on a number of factors, including the type of cable, cable jacket, cable length, cable twist density, proximity of adjacent cables, and connectors, and EMI. Patch panels and connecting hardware are also affected by ANEXT.

With Alien Crosstalk, the affected cable is called the victim cable. The surrounding cables are the disturber cables.

There are a number of ways to mitigate the effects of ANEXT in CAT6A runs. According to the standards, ANEXT can be improved by laying CAT6A UTP cable loosely in pathways and raceways with space between the cables. This contrasts to the tightly bundled runs of CAT6/5e cable that we are used to. The tight bundles present a worst-case scenario of six cables around one, thus the center cable would be adversely affected by ANEXT. CAT6A UTP cable needs to be tested for ANEXT. This is a complex and time-consuming process in which all possible wire-pair combinations need to be tested for ANEXT and far-end ANEXT. It can take 50 minutes to test one link in a bundle of 24 CAT 6A UTP cables.

To virtually eliminate the problem of ANEXT, you can use CAT6A F/UTP cable. The F indicates an outer foil shield encasing four unshielded twisted pairs. This cable is also a good choice when security is an issue because it doesn’t emit signals. In addition, CAT6A F/UTP cable works well in noisy environments with a lot of EMI/RFI.

Installation of CAT6A F/UTP is simpler, too, because the cable features a smaller outside diameter than CAT6A UTP. Its construction makes it easier to pull and more resilient. The cable also has a smaller diameter so you can run more cables in a conduit or pathway, and have greater patch panel port density.

For more information, see the CAT6A F/UTP vs. UTP: What You Need to Know white paper in the Resources section at blackbox.com. collapse


Black Box Explains…CAT6A UTP vs. F/UTP.

CAT6A is currently the cable of choice for future-proofing cabling installations and for 10-GbE networks.

There are two types of CAT6A cable, unshielded (UTP) and shielded (F/UTP). F/UTP denotes foiled/unshielded... more/see it nowtwisted pair and consists of four unshielded twisted pairs encased in an overall foil shield. This is not to be confused with an S/FTP (screened/foiled twisted pair) cable, which has four individually shielded twisted pairs encased in an overall braided shield.

CAT6A UTP
CAT6A UTP is constructed in a certain way to help eliminate crosstalk and ANEXT. (ANEXT is the measurement of the signal coupling between wire pairs in different and adjacent cables.) This includes larger conductors (23 AWG minimum), tighter twists, an extra internal airspace, an internal separator between the pairs, and a thicker outer jacket. These features also increase the outer diameter of the cable, typically to .35 inches in diameter, up from .25 inches for CAT6 cable. This increased diameter creates a greater distance between pairs in adjacent links, thus reducing the between-channel signal coupling. But CAT6A UTP cable is still affected by ANEXT.

According to the standards, ANEXT can be improved by laying CAT6A UTP cable loosely in pathways and raceways with space between the cables. This contrasts to the tightly bundled runs of CAT6/5e cable we are used to. The tight bundles present a worst-case scenario of six cables around one, thus the center cable would be adversely affected by ANEXT. Testing for ANEXT is a complex and time-consuming process where all possible wire-pair combinations are checked. It can take up to 50 minutes to test one link in a bundle of 24 CAT6A UTP cables.

CAT6A F/UTP
CAT6A F/UTP denotes foiled/unshielded twisted pairs and consists of four unshielded twisted pairs encased in an overall foil shield. ANEXT, and the time needed to test for it, can be greatly reduced, if not eliminated completely, by using CAT6A F/UTP. The foil shield acts as a barrier preventing external EMI/RFI from coupling onto the twisted pairs. It also prevents data signals from leaking out of the cable, making the cable more difficult to tap and better for secure installations. Studies also have shown that CAT6A F/UTP cable provides significantly more headroom (as much as 20 dB) than CAT6A UTP in 10-GbE over copper systems.

Bigger isn't always better.
CAT6A UTP cable has an overall allowable diameter of 0.354 inches. CAT6A F/UTP cable has an average outside diameter of 0.265–0.30 inches. That’s smaller than the smallest CAT6A UTP cable. An increase in the outside diameter (O.D.) of 0.1 inch, from 0.25 inches to 0.35 inches for example, represents a 21% increase in fill volume. In general, CAT6A F/UTP cable provides a minimum of 35% more fill capacity that CAT6A UTP cable.

Also because of its large diameter, CAT6A UTP requires a larger bend radius, more pathways, less dense patch panel connections, and extensive ANEXT testing.

CAT6A F/UTP cable is actually easier to handle, requires less bend radius, and uses smaller pathways. In addition, innovations in connector technology has made terminating CAT6A F/UTP cable simpler. In terms of grounding, the requirements for both UTP and F/UTP cable fall under TIA/EIA J-STD-607-A Commercial Building Grounding (Earthing) and Bonding Requirements for Telecommunications.

The advantages of CAT6A F/UTP vs. UTP
In summary, there are a number of advantages of using CAT6A F/UTP over CAT6A UTP in 10-GbE networks.

1. Shielding eliminates ANEXT and EMI/RFI problems and testing.
2. Data line security is enhanced because of shielding.
3. Lighter, slimmer cable provides higher port density.
4. Smaller outside diameter cable is easier to handle and reduces installation costs.
5. Shielded cable uses less space in conduits.

For more information, see the CAT6A F/UTP vs. UTP: What You Need to Know white paper in the Resources section at blackbox.com. collapse


Black Box Explains...Augmented Category 6 (CAT6A).


Augmented Category 6 (CAT6a)–Class Ea was ratified in February 2008. This standard calls for 10-Gigabit Ethernet data transmission over a 4-pair copper cabling system up to 100 meters. CAT6a extends... more/see it nowCAT6 electrical specifications from 250 MHz to 500 MHz. It introduces the ANEXT requirement. It also replaces the term Equal Level Far-End Crosstalk (ELFEXT) with Attenuation to Crosstalk Ratio, Far-End (ACRF) to mesh with ISO terminology. CAT6a provides improved insertion loss over CAT6. It is a good choice for noisy environments with lots of EMI. CAT6a is also well-suited for use with PoE+.

CAT6a UTP cable is significantly larger than CAT6 cable. It features larger conductors, usually 22 AWG, and is designed with more space between the pairs to minimize ANEXT. The outside diameter of CAT6a cable averages 0.29–0.35" compared to 0.21–0.24" for CAT6 cable. This reduces number of cables you can fit in a conduit. At a 40% fill ratio, you can run three CAT6a cables in a 3/4" conduit vs. five CAT6 cables.

There are two types of CAT6a cable, UTP and F/UTP.