  • GigaBase 350 CAT5e, 350-MHz Solid Bulk Cable (PVC, Black) PDF Drawing
    PDF Drawing of the EYN861A-PB-1000 (1)
 

Black Box Explains...Cable termination.


Carefully remove the jacketing from the cable and expose one inch of the insulated wire conductors. Do not remove any insulation from the conductors. When the... more/see it nowRJ-45 connector is crimped, the contacts inside will pierce the conductor insulation.


Untwist the wires to within 1/8" of the jacket. Arrange the wires according to the cable spec (568B in this case). Flatten and align the wires. Make one straight cut across all the conductors, removing approximately 1/2" to ensure the ends are of equal length.


Slide the wires into a connector. The cable jacket should extend into the connector about 1/4" for strain relief. Orient the wires so connector Pin 1 aligns with cable Pin 1, etc. Hold the connector in front of you. With the locking tab down, Pin 1 is on the far left.


Insert the connector into a crimp tool. Make sure you’re using the proper die. Firmly squeeze the handles. They’ll lock in a ratcheting action. A final click indicates the connector is firmly latched.


Check your work using a continuity tester or cable certifier rated for the cable standard you’re installing. Your tester should be able to check for shorts, opens, or miswires.


collapse

  • Pdf Drawing... 
  • GigaTrue%XAE 550 CAT6, 550-MHz Solid Bulk Cable (4-Pair, PVC, Gray) PDF Drawing
    PDF Drawing for the EYN876A-PB-1000 (1)
 

Black Box Explains...RS-232.

RS-232, also known as RS-232C and TIA/EIA-232-E, is a group of electrical, functional, and mechanical specifications for serial interfaces between computers, terminals, and peripherals. The RS-232 standard was developed by... more/see it nowthe Electrical Industries Association (EIA), and defines requirements for connecting data communications equipment (DCE)—modems, converters, etc.—and data terminal equipment (DTE)—computers, controllers, etc.) devices. RS-232 transmits data at speeds up to 115 Kbps and over distances up to 50 feet (15.2 m).

The standard, which is functionally equivalent to ITU V.24/V.28, specifies the workings of the interface, circuitry, and connector pinning. Both sync and async binary data transmission fall under RS-232. Although RS-232 is sometimes still used to transmit data from PCs to peripheral devices, the most common uses today are for network console ports and for industrial devices.

Even though RS-232 is a “standard,” you can’t necessarily expect seamless communication between two RS-232 devices. Why? Because different devices have different circuitry or pinning, and different wires may be designated to perform different functions.

The typical RS-232 connector is DB25, but some PCs and other data communication devices have DB9 connectors and many newer devices have RJ-45 RS-232 ports. To connect 9-pin PC ports or RJ-45 to devices with 25-pin connectors, you will require a simple adapter cable. collapse

  • Pdf Drawing... 
  • GigaBase 350 CAT5e, 350-MHz Solid Bulk Cable (Plenum, Gray) PDF Drawing
    PDF Drawing of the EYN856A-PB-1000 (1)
 

Black Box Explains…Component vs. channel testing.

When using a Category 6 system, the full specification includes the testing of each part individually and in an end-to-end-channel. Because CAT6 is an open standard, products from different vendors... more/see it nowshould work together.

Channel testing includes patch cable, bulk cable, jacks, patch panels, etc. These tests cover a number of measurements, including: attenuation, NEXT, PS-NEXT, EL-FEXT, ACR, PS-ACR, EL-FEXT, PS-ELFEXT, and Return Loss. Products that are tested together should work together as specified. In theory, products from all manufacturers are interchangeable. But, if products from different manufacturers are inserted in a channel, end-to-end CAT6 performance may be compromised.

Component testing, on the other hand, is much stricter even though only two characteristics are measured: crosstalk and return loss. Although all CAT6 products should be interchangeable, products labeled as component are guaranteed to perform to a CAT6 level in a channel with products from different manufacturers.

For more information on cable, channel, and component specs, see below.

Buyer’s Guide: CAT5e vs. CAT6 Cable

Standard — CAT5e: TIA-568-B.2; CAT6: TIA-568-B.2-1

Frequency — CAT5e: 100 MHz; CAT6: 250 MHz

Attenuation (maximum at 100 MHz) —
Cable: CAT5e: 22 dB; CAT6: 19.8 dB
Connector: CAT5e: 0.4 dB; CAT6: 0.2 dB
Channel: CAT5e: 24.0 dB; CAT6: 21.3 dB

NEXT (minimum at 100 MHz) —
Cable: CAT5e: 35.3 dB; CAT6: 44.3 dB
Connector: CAT5e: 43.0 dB; CAT6: 54.0 dB
Channel: CAT5e: 30.1 dB; CAT6: 39.9 dB

PS-NEXT (minimum at 100 MHz) — 32.3 dB 42.3 dB

EL-FEXT (minimum at 100 MHz) —
Cable: CAT5e: 23.8 dB; CAT6: 27.8 dB
Connector: CAT5e: 35.1 dB; CAT6: 43.1 dB
Channel: CAT5e: 17.4 dB; CAT6: 23.3 dB

PS-ELFEXT (minimum at 100 MHz) — CAT5e: 20.8 dB; CAT6: 24.8 dB

Return Loss (minimum at 100 MHz) —
Cable: CAT5e: 20.1 dB; CAT6: 20.1 dB
Connector: CAT5e: 20.0 dB: CAT6: 24.0 dB
Channel: CAT5e: 10.0 dB; CAT6: 12.0 dB

Characteristic Impedance — Both: 100 ohms ± 15%

Delay Skew (maximum per 100 m) — Both: 45 ns

NOTE: In Attenuation testing, the lower the number, the better. In NEXT, EL-FEXT, and Return Loss testing, the higher the number, the better. collapse

  • Pdf Drawing... 
  • GigaBase 350 CAT5e, 350-MHz Solid Bulk Cable (PVC, Red) PDF Drawing
    PDF Drawing of the EYN849A-PB-1000 (1)
 
  • Pdf Drawing... 
  • GigaTrue 550 CAT6, 550-MHz Solid Bulk Cable (4-Pair, PVC, Black) PDF Drawing
    PDF Drawing for the EYN880A-PB-1000 (1)
 
  • Pdf Drawing... 
  • GigaBase 350 CAT5e, 350-MHz Solid Bulk Cable (Plenum, Black) PDF Drawing
    PDF Drawing of the EYN860A-PB-1000 (1)
 
  • Pdf Drawing... 
  • GigaBase 350 CAT5e, 350-MHz Solid Bulk Cable (PVC, Yellow) PDF Drawing
    PDF Drawing of the EYN855A-PB-1000 (1)
 