Categories (x) > Cables (x)

Results 111-120 of 322 << < 11 12 13 14 15 > >> 

Black Box Explains...The MPO connector.

MPO stands for multifiber push-on connector. It is a connector for multifiber ribbon cable that generally contains 6, 8, 12, or 24 fibers. It is defined by IEC-61754-7 and EIA/TIA-604-5-D,... more/see it nowalso known as FOCIS 5. The MPO connector, combined with lightweight ribbon cable, represents a huge technological advance over traditional multifiber cables. It’s lighter, more compact, easier to install, and less expensive.

A single MPO connector replaces up to 24 standard connectors. This very high density means lower space requirements and reduced costs for your installation. Traditional, tight-buffered multifiber cable needs to have each fiber individually terminated by a skilled technician. But MPO fiber optic cable, which carries multiple fibers, comes preterminated. Just plug it in and you’re ready to go.BR>
MPO connectors feature an intuitive push-pull latching sleeve mechanism with an audible click upon connection and are easy to use. The MPO connector is similar to the MT-RJ connector. The MPO’s ferrule surface of 2.45 x 6.40 mm is slightly bigger than the MT-RJ’s, and the latching mechanism works with a sliding sleeve latch rather than a push-in latch.

The MPO connector can be either male or female. You can tell the male connector by the two alignment pins protruding from the end of the ferrule. The MPO ferrule is generally flat for multimode applications and angled for single-mode applications.

MPO connectors are also commonly called MTP® connectors, which is a registered trademark of US Conec. The MTP connector is an MPO connector collapse


Product Data Sheets (pdf)...MT-RJ Multimode Fiber Optic Cable




Black Box Explains... Digital Optic Cable

Many new, high-quality Mini Disc, pro-audio, DAT (Digital Audio Tape), CD, DVD, and laser disc players, as well as digital amplifiers, DSS satellite receivers, and computer sound cards, are manufactured... more/see it nowwith digital optical output connectors.

These connectors attach to optical cables, which are constructed with a PVC jacket and a plastic core. The cables transfer information accurately over short distances via digital light signals with low loss and no distortion.

Digital optical cable with plastic-core construction is less expensive than fiber optic cable with a glass core, but it still provides the benefits of optical transmission over short distances.

Digital audio makes it possible to use high-quality digital-to-analog converters, which help to maintain the integrity of sound signals from high-end electronic devices.

The two types of connectors associated with digital optical transmission are TOSLINK®, a Toshiba® trademark, and the 3.5-mm Mini Plug connector. collapse


Black Box Explains... RJ-48

An RJ-48 plug is often mistaken for RJ-45. On the outside, the two look identical—both are housed in a miniature 8-position jack. The difference is in the pairing of the... more/see it nowwires.

In RJ-48, two of the wires are for transmit, two are for receive, and two are for the drain. The last two wires are reserved for future use.

There are three subsets within RJ-48: RJ-48C, RJ-48X, and RJ-48S.

RJ-48C and RJ-48X are very similar. Both use lines 1, 2, 4, and 5 and connect T1 lines. The RJ-48C is more common. The difference is that RJ-48X connectors have shorting bars.

RJ-48S uses lines 1, 2, 7, and 8. It connects 56K DDS lines. collapse

  • Pdf Drawing... 
  • GigaBase 350 CAT5e, 350-MHz Solid Bulk Cable (PVC, Green) PDF Drawing
    PDF Drawing of the EYN859A-PB-1000 (1)
 
  • Manual... 
  • 3 Channel DVI Extender
    Installation/User Guide (12/6/2013)
 
  • Pdf Drawing... 
  • GigaBase 350 CAT5e Patch Cable with Snagless Boots (Yellow) PDF Drawing
    PDF Drawing for the EVNSL84 series.
 

Black Box Explains…CAT6A UTP vs. F/UTP.

CAT6A is currently the cable of choice for future-proofing cabling installations and for 10-GbE networks.

There are two types of CAT6A cable, unshielded (UTP) and shielded (F/UTP). F/UTP denotes foiled/unshielded... more/see it nowtwisted pair and consists of four unshielded twisted pairs encased in an overall foil shield. This is not to be confused with an S/FTP (screened/foiled twisted pair) cable, which has four individually shielded twisted pairs encased in an overall braided shield.

CAT6A UTP
CAT6A UTP is constructed in a certain way to help eliminate crosstalk and ANEXT. (ANEXT is the measurement of the signal coupling between wire pairs in different and adjacent cables.) This includes larger conductors (23 AWG minimum), tighter twists, an extra internal airspace, an internal separator between the pairs, and a thicker outer jacket. These features also increase the outer diameter of the cable, typically to .35 inches in diameter, up from .25 inches for CAT6 cable. This increased diameter creates a greater distance between pairs in adjacent links, thus reducing the between-channel signal coupling. But CAT6A UTP cable is still affected by ANEXT.

According to the standards, ANEXT can be improved by laying CAT6A UTP cable loosely in pathways and raceways with space between the cables. This contrasts to the tightly bundled runs of CAT6/5e cable we are used to. The tight bundles present a worst-case scenario of six cables around one, thus the center cable would be adversely affected by ANEXT. Testing for ANEXT is a complex and time-consuming process where all possible wire-pair combinations are checked. It can take up to 50 minutes to test one link in a bundle of 24 CAT6A UTP cables.

CAT6A F/UTP
CAT6A F/UTP denotes foiled/unshielded twisted pairs and consists of four unshielded twisted pairs encased in an overall foil shield. ANEXT, and the time needed to test for it, can be greatly reduced, if not eliminated completely, by using CAT6A F/UTP. The foil shield acts as a barrier preventing external EMI/RFI from coupling onto the twisted pairs. It also prevents data signals from leaking out of the cable, making the cable more difficult to tap and better for secure installations. Studies also have shown that CAT6A F/UTP cable provides significantly more headroom (as much as 20 dB) than CAT6A UTP in 10-GbE over copper systems.

Bigger isn't always better.
CAT6A UTP cable has an overall allowable diameter of 0.354 inches. CAT6A F/UTP cable has an average outside diameter of 0.265–0.30 inches. That’s smaller than the smallest CAT6A UTP cable. An increase in the outside diameter (O.D.) of 0.1 inch, from 0.25 inches to 0.35 inches for example, represents a 21% increase in fill volume. In general, CAT6A F/UTP cable provides a minimum of 35% more fill capacity that CAT6A UTP cable.

Also because of its large diameter, CAT6A UTP requires a larger bend radius, more pathways, less dense patch panel connections, and extensive ANEXT testing.

CAT6A F/UTP cable is actually easier to handle, requires less bend radius, and uses smaller pathways. In addition, innovations in connector technology has made terminating CAT6A F/UTP cable simpler. In terms of grounding, the requirements for both UTP and F/UTP cable fall under TIA/EIA J-STD-607-A Commercial Building Grounding (Earthing) and Bonding Requirements for Telecommunications.

The advantages of CAT6A F/UTP vs. UTP
In summary, there are a number of advantages of using CAT6A F/UTP over CAT6A UTP in 10-GbE networks.

1. Shielding eliminates ANEXT and EMI/RFI problems and testing.
2. Data line security is enhanced because of shielding.
3. Lighter, slimmer cable provides higher port density.
4. Smaller outside diameter cable is easier to handle and reduces installation costs.
5. Shielded cable uses less space in conduits.

For more information, see the CAT6A F/UTP vs. UTP: What You Need to Know white paper in the Resources section at blackbox.com. collapse

Results 111-120 of 322 << < 11 12 13 14 15 > >> 