Black Box Explains... Crosstalk.

One of the most important cable measurements is Near-End Crosstalk (NEXT). It’s signal interference from one pair that adversely affects another pair on the same end.

Not only can crosstalk... more/see it nowoccur between adjacent wire pairs (“pair-to-pair NEXT“), but all other pairs in a UTP cable can also contribute their own levels of both near-end and far-end crosstalk, multiplying the adverse effects of this interference onto a transmitting or receiving wire pair.

Because such compounded levels of interference can prove crippling in high-speed networks, some cable manufacturers have begun listing Power Sum NEXT (PS-NEXT), FEXT, ELFEXT, and PS-ELFEXT ratings for their CAT5e and CAT6 cables. Here are explanations of the different types of measurements:

NEXT measures an unwanted signal transmitted from one pair to another on the near end.

PS-NEXT (Power Sum crosstalk) is a more rigorous crosstalk measurement that includes the total sum of all interference that can possibly occur between one pair and all the adjacent pairs in the same cable sheath. It measures the unwanted signals from multiple pairs at the near end onto another pair at the near end.

FEXT (Far-End crosstalk) measures an unwanted signal from a pair transmitting on the near end onto a pair at the far end. This measurement takes full-duplex operation into account where signals are generated simultaneously on both ends.

ELFEXT (Equal-Level Far-End Crosstalk) measures the FEXT in relation to the received signal level measured on that same pair. It basically measures interference without the effects of attenuation—the equal level.

PS-ELFEXT (Power Sum Equal-Level Far-End Crosstalk), an increasingly common measurement, measures the total sum of all intereference from pairs on the far end to a pair on the near end without the effects of attenuation. collapse



Black Box Explains...10-GbE, CAT6A, and ANEXT.

The IEEE released the 802.3an 10GBASE-T standard in June 2006. This standard specifies 10-Gbps data transmission over four-pair copper cabling. 10-Gigabit Ethernet (10-GbE) transmission includes up to 37 meters of... more/see it nowCAT6 cable (with installation mitigation techniques), 100 meters of Augmented Category 6 (CAT6A) UTP or F/UTP cable or 100 meters of S/FTP CAT7/Class F cable.

CAT6A is the ANSI/TIA 10-Gigabit Ethernet (10-GbE) over copper standard. Its requirements are covered in ANSI/TIA-568-C.2 (Balanced Twisted-Pair Communications Cabling and Components Standard) published in August 2009. It defines 10-Gigabit data transmission over a 4-connector twisted-pair CAT6A copper cable for a distance of 100 meters.

Category 6A cabling is designed to support next-generation applications, including the transfer of large amounts of data at high speeds, up to 10 Gbps. CAT6A extends electrical specifications to 500 MHz from 250 MHz for CAT6 cabling. CAT6A cables are fully backward compatible with previous categories, including CAT6 and 5e. Category 6A is also designed to support bundled cable installations up to 100 meters and PoE+ low-power implementations. The standard includes the performance parameter, Alien Crosstalk (ANEXT). Because of its higher performance transmission speeds and higher MHz rating, CAT6A cable needs to be tested for external noise outside the cable, which wasn’t a concern with previous cabling categories. CAT6A UTP also has a much larger diameter than previous cables.

Alien crosstalk (ANEXT) is a critical and unique measurement in 10-GbE systems. Crosstalk, measured in 10/100/1000BASE-T systems, is the mixing of signals between wire pairs within a cable. Alien Crosstalk, in 10-GbE systems, is the measurement of the unwanted signal coupling between wire pairs in different and adjacent cables or from one balanced twisted-pair component, channel, or permanent link to another.

The amount of ANEXT depends on a number of factors, including the type of cable, cable jacket, cable length, cable twist density, proximity of adjacent cables, and connectors, and EMI. Patch panels and connecting hardware are also affected by ANEXT.

With Alien Crosstalk, the affected cable is called the victim cable. The surrounding cables are the disturber cables.

There are a number of ways to mitigate the effects of ANEXT in CAT6A runs. According to the standards, ANEXT can be improved by laying CAT6A UTP cable loosely in pathways and raceways with space between the cables. This contrasts to the tightly bundled runs of CAT6/5e cable that we are used to. The tight bundles present a worst-case scenario of six cables around one, thus the center cable would be adversely affected by ANEXT. CAT6A UTP cable needs to be tested for ANEXT. This is a complex and time-consuming process in which all possible wire-pair combinations need to be tested for ANEXT and far-end ANEXT. It can take 50 minutes to test one link in a bundle of 24 CAT 6A UTP cables.

To virtually eliminate the problem of ANEXT, you can use CAT6A F/UTP cable. The F indicates an outer foil shield encasing four unshielded twisted pairs. This cable is also a good choice when security is an issue because it doesn’t emit signals. In addition, CAT6A F/UTP cable works well in noisy environments with a lot of EMI/RFI.

Installation of CAT6A F/UTP is simpler, too, because the cable features a smaller outside diameter than CAT6A UTP. Its construction makes it easier to pull and more resilient. The cable also has a smaller diameter so you can run more cables in a conduit or pathway, and have greater patch panel port density.

For more information, see the CAT6A F/UTP vs. UTP: What You Need to Know white paper in the Resources section at blackbox.com. collapse

  • Pdf Drawing... 
  • GigaTrue%XAE CAT6 Component 550-MHz Patch Cable with Molded Boots (Purple) PDF Drawing
    PDF Drawing for EVNSL678-0003, EVNSL678-0005, EVNSL678-0007, EVNSL678-0010, EVNSL678-0015, and EVNSL68-0020
 

  • Manual... 
  • CAT5e Value Line Patch Cable (Stranded) User Manual
    User Manual for the ICD202A (Version 2)
 
  • Pdf Drawing... 
  • GigaTrue%XAE CAT6 Component 550-MHz Patch Cable with Molded Boots (Orange) PDF Drawing
    PDF Drawing for EVNSL679-0003, EVNSL679-0005, EVNSL679-0007, EVNSL679-0010, EVNSL679-0015, and EVNSL69-0020
 

Product Data Sheets (pdf)...GigaBase CAT5e Channel Solution


Black Box Explains...10GBASE-T standard.

In June 2006, the IEEE approved the standard for 10 Gigabit/sec Ethernet, or 10GBASE-T (10-GbE). 10-GbE transmission requires a bandwidth of 500 MHz.

The 10-GbE standards.
The cabling industry is developing... more/see it nowtwo different standards that can be used in 10-GbE applications. One is for use with Category 6 (CAT6) cable, and one is for Augmented Category 6 (CAT6a).

Alien Crosstalk.
Before discussing the standards, a definition of Alien Crosstalk is needed.

Alien Crosstalk (ANEXT) is a critical measurement unique to 10-GbE systems. Crosstalk, measured in 10/100/1000BASE-T systems, is the mixing of signals between wire pairs within a cable. Alien Crosstalk is the measurement of the signal coupling between wire pairs in different, adjacent cables.

The amount of ANEXT depends on a number of factors, including the promixity of adjacent cables and connectors, the cable length, cable twist density, and EMI. Patch panels and connecting hardware are also affected by ANEXT.

With ANEXT, the affected cable is called the disturbed or victim cable. The surrounding cables are the disturbers.

10-GbE using CAT6.
The first set of standards defines cabling performance when using Category 6/Class E cabling for 10-GbE applications. The TIA/EIA version will be the Technical Systems Bulletin 155 (TSB 155). ISO/IEC TR 24750 is a technical report to be used for measuring existing Class E systems.

No matter what the cable length is, CAT6 cable must meet 10-GbE electrical and ANEXT specifications up to 500 MHz. However, the CAT6 standard now specifies measurements only to 250 MHz, and it does not have an ANEXT requirement. There is no guarantee CAT6 can support a 10-GbE system. But the TSB provides guidelines for ways to help mitigate ANEXT. One way to lessen or eliminate ANEXT is to use shielded equipment and cables. Another way is to follow installation guidelines, such as using non-adjacent patch panels, separating equipment cords, unbundling horizontal cabling, etc.

10GbE using CAT6a.
The second set of standards will define Augmented Category 6 (CAT6a) and Augmented Class E (Class Ea) cabling. The newer, augmented cabling systems are designed to support 10-GbE over a 100-meter horizontal channel.

The TIA/EIA version is in draft and will be published as ANSI/TIA/EIA-568B.2-AD10. It recognizes both UTP and STP CAT6a systems. It also extends CAT6 electrical parameters such as NEXT, FEXT, return loss, insertion loss, and more to 500 MHz. It specifies near- and far-end Alien Crosstalk (ANEXT, AFEXT) to 500 MHz. It also goes beyond IEEE 802.3an by establishing the electrical requirements for the permanent link and cabling components. The ISO Class Ea standard will be published in a new edition of the 11801 standard.

These standards specify requirements for each component in the channel, such as cable and connecting hardware, as well as for the permanent link and the channel. collapse