Black Box Explains...Shielded vs. unshielded cable.

The environment determines whether cable should be shielded or unshielded.

Shielding is the sheath surrounding and protecting the cable wires from electromagnetic leakage and interference. Sources of this electromagnetic activity... more/see it now(EMI)—commonly referred to as noise—include elevator motors, fluorescent lights, generators, air conditioners, and photocopiers. To protect data in areas with high EMI, choose a shielded cable.

Foil is the most basic cable shield, but a copper-braid shield provides more protection. Shielding also protects cables from rodent damage. Use a foil-shielded cable in busy office or retail environments. For industrial environments, you might want to choose a copper-braid shield.

For quiet office environments, choose unshielded cable. collapse


Black Box Explains…CAT6A UTP vs. F/UTP.

CAT6A is currently the cable of choice for future-proofing cabling installations and for 10-GbE networks.

There are two types of CAT6A cable, unshielded (UTP) and shielded (F/UTP). F/UTP denotes foiled/unshielded... more/see it nowtwisted pair and consists of four unshielded twisted pairs encased in an overall foil shield. This is not to be confused with an S/FTP (screened/foiled twisted pair) cable, which has four individually shielded twisted pairs encased in an overall braided shield.

CAT6A UTP
CAT6A UTP is constructed in a certain way to help eliminate crosstalk and ANEXT. (ANEXT is the measurement of the signal coupling between wire pairs in different and adjacent cables.) This includes larger conductors (23 AWG minimum), tighter twists, an extra internal airspace, an internal separator between the pairs, and a thicker outer jacket. These features also increase the outer diameter of the cable, typically to .35 inches in diameter, up from .25 inches for CAT6 cable. This increased diameter creates a greater distance between pairs in adjacent links, thus reducing the between-channel signal coupling. But CAT6A UTP cable is still affected by ANEXT.

According to the standards, ANEXT can be improved by laying CAT6A UTP cable loosely in pathways and raceways with space between the cables. This contrasts to the tightly bundled runs of CAT6/5e cable we are used to. The tight bundles present a worst-case scenario of six cables around one, thus the center cable would be adversely affected by ANEXT. Testing for ANEXT is a complex and time-consuming process where all possible wire-pair combinations are checked. It can take up to 50 minutes to test one link in a bundle of 24 CAT6A UTP cables.

CAT6A F/UTP
CAT6A F/UTP denotes foiled/unshielded twisted pairs and consists of four unshielded twisted pairs encased in an overall foil shield. ANEXT, and the time needed to test for it, can be greatly reduced, if not eliminated completely, by using CAT6A F/UTP. The foil shield acts as a barrier preventing external EMI/RFI from coupling onto the twisted pairs. It also prevents data signals from leaking out of the cable, making the cable more difficult to tap and better for secure installations. Studies also have shown that CAT6A F/UTP cable provides significantly more headroom (as much as 20 dB) than CAT6A UTP in 10-GbE over copper systems.

Bigger isn't always better.
CAT6A UTP cable has an overall allowable diameter of 0.354 inches. CAT6A F/UTP cable has an average outside diameter of 0.265–0.30 inches. That’s smaller than the smallest CAT6A UTP cable. An increase in the outside diameter (O.D.) of 0.1 inch, from 0.25 inches to 0.35 inches for example, represents a 21% increase in fill volume. In general, CAT6A F/UTP cable provides a minimum of 35% more fill capacity that CAT6A UTP cable.

Also because of its large diameter, CAT6A UTP requires a larger bend radius, more pathways, less dense patch panel connections, and extensive ANEXT testing.

CAT6A F/UTP cable is actually easier to handle, requires less bend radius, and uses smaller pathways. In addition, innovations in connector technology has made terminating CAT6A F/UTP cable simpler. In terms of grounding, the requirements for both UTP and F/UTP cable fall under TIA/EIA J-STD-607-A Commercial Building Grounding (Earthing) and Bonding Requirements for Telecommunications.

The advantages of CAT6A F/UTP vs. UTP
In summary, there are a number of advantages of using CAT6A F/UTP over CAT6A UTP in 10-GbE networks.

1. Shielding eliminates ANEXT and EMI/RFI problems and testing.
2. Data line security is enhanced because of shielding.
3. Lighter, slimmer cable provides higher port density.
4. Smaller outside diameter cable is easier to handle and reduces installation costs.
5. Shielded cable uses less space in conduits.

For more information, see the CAT6A F/UTP vs. UTP: What You Need to Know white paper in the Resources section at blackbox.com. collapse


Black Box Explains...Cable termination.


Carefully remove the jacketing from the cable and expose one inch of the insulated wire conductors. Do not remove any insulation from the conductors. When the... more/see it nowRJ-45 connector is crimped, the contacts inside will pierce the conductor insulation.


Untwist the wires to within 1/8" of the jacket. Arrange the wires according to the cable spec (568B in this case). Flatten and align the wires. Make one straight cut across all the conductors, removing approximately 1/2" to ensure the ends are of equal length.


Slide the wires into a connector. The cable jacket should extend into the connector about 1/4" for strain relief. Orient the wires so connector Pin 1 aligns with cable Pin 1, etc. Hold the connector in front of you. With the locking tab down, Pin 1 is on the far left.


Insert the connector into a crimp tool. Make sure you’re using the proper die. Firmly squeeze the handles. They’ll lock in a ratcheting action. A final click indicates the connector is firmly latched.


Check your work using a continuity tester or cable certifier rated for the cable standard you’re installing. Your tester should be able to check for shorts, opens, or miswires.


collapse


Black Box Explains…Component vs. channel testing.

When using a Category 6 system, the full specification includes the testing of each part individually and in an end-to-end-channel. Because CAT6 is an open standard, products from different vendors... more/see it nowshould work together.

Channel testing includes patch cable, bulk cable, jacks, patch panels, etc. These tests cover a number of measurements, including: attenuation, NEXT, PS-NEXT, EL-FEXT, ACR, PS-ACR, EL-FEXT, PS-ELFEXT, and Return Loss. Products that are tested together should work together as specified. In theory, products from all manufacturers are interchangeable. But, if products from different manufacturers are inserted in a channel, end-to-end CAT6 performance may be compromised.

Component testing, on the other hand, is much stricter even though only two characteristics are measured: crosstalk and return loss. Although all CAT6 products should be interchangeable, products labeled as component are guaranteed to perform to a CAT6 level in a channel with products from different manufacturers.

For more information on cable, channel, and component specs, see below.

Buyer’s Guide: CAT5e vs. CAT6 Cable

Standard — CAT5e: TIA-568-B.2; CAT6: TIA-568-B.2-1

Frequency — CAT5e: 100 MHz; CAT6: 250 MHz

Attenuation (maximum at 100 MHz) —
Cable: CAT5e: 22 dB; CAT6: 19.8 dB
Connector: CAT5e: 0.4 dB; CAT6: 0.2 dB
Channel: CAT5e: 24.0 dB; CAT6: 21.3 dB

NEXT (minimum at 100 MHz) —
Cable: CAT5e: 35.3 dB; CAT6: 44.3 dB
Connector: CAT5e: 43.0 dB; CAT6: 54.0 dB
Channel: CAT5e: 30.1 dB; CAT6: 39.9 dB

PS-NEXT (minimum at 100 MHz) — 32.3 dB 42.3 dB

EL-FEXT (minimum at 100 MHz) —
Cable: CAT5e: 23.8 dB; CAT6: 27.8 dB
Connector: CAT5e: 35.1 dB; CAT6: 43.1 dB
Channel: CAT5e: 17.4 dB; CAT6: 23.3 dB

PS-ELFEXT (minimum at 100 MHz) — CAT5e: 20.8 dB; CAT6: 24.8 dB

Return Loss (minimum at 100 MHz) —
Cable: CAT5e: 20.1 dB; CAT6: 20.1 dB
Connector: CAT5e: 20.0 dB: CAT6: 24.0 dB
Channel: CAT5e: 10.0 dB; CAT6: 12.0 dB

Characteristic Impedance — Both: 100 ohms ± 15%

Delay Skew (maximum per 100 m) — Both: 45 ns

NOTE: In Attenuation testing, the lower the number, the better. In NEXT, EL-FEXT, and Return Loss testing, the higher the number, the better. collapse


Black Box Explains...What to look for in a channel solution.


Channel solution. You hear the term a lot these days to describe complete copper or fiber cabling systems. But what exactly is a channel solution and what are its benefits?... more/see it now

A definition.
A channel solution is a cabling system from the data center to the desktop where every cable, jack, and patch panel is designed to work together and give you consistent end-to-end performance when compared with the EIA/TIA requirements.

Its benefits.
A channel solution is beneficial because you have some assurance that your cabling components will perform as specified. Without that assurance, one part may not be doing its job, so your entire system may not be performing up to standard, which is a problem — especially if you rely on bandwidth-heavy links for video and voice.

What to look for.
There are a lot of channel solutions advertised on the Internet and elsewhere. So what exactly should you be looking for?

For one, make sure it’s a fully tested, guaranteed channel solution. The facts show an inferior cabling system can cause up to 70 percent of network downtime — even though it usually represents only 5 percent of an initial network investment. So don’t risk widespread failure by skimping on a system that doesn’t offer guaranteed channel performance. You need to make sure the products are engineered to meet or go beyond the key measurements for CAT5e or CAT6 performance.

And, sure, they may be designed to work together, but does the supplier absolutely guarantee how well they perform as part of a channel — end to end? Don’t just rely on what the supplier says. They may claim their products meet CAT5e or CAT6 requirements, but the proof is in the performance. Start by asking if the channel solution is independently tested and certified by a reputable third party. There are a lot of suppliers out there who don’t have the trademarked ETL approval logo, for example.

What ETL Verified means.
The ETL logo certifies that a channel solution has been found to be in compliance with recognized standards. To ensure consistent top quality, Black Box participates in independent third-party testing by InterTek Testing Services/ETL Semko, Inc. Once a quarter, an Intertek inspector visits Black Box and randomly selects cable and cabling products for testing.

The GigaTrue® CAT6 and GigaBase® CAT5e Solid Bulk Cable are ETL Verified at the component level to verify that they conform to the applicable industry standards. The GigaTrue® CAT6 and GigaBase® CAT5e Channels, consisting of bulk cable, patch cable, jacks, patch panels, and wiring blocks, are tested and verified according to industry standards in a LAN environment under InterTek’s Cabling System Channel Verification Program. For the latest test results, contact our FREE Tech Support. collapse