Black Box Explains...10-GbE, CAT6A, and ANEXT.

The IEEE released the 802.3an 10GBASE-T standard in June 2006. This standard specifies 10-Gbps data transmission over four-pair copper cabling. 10-Gigabit Ethernet (10-GbE) transmission includes up to 37 meters of... more/see it nowCAT6 cable (with installation mitigation techniques), 100 meters of Augmented Category 6 (CAT6A) UTP or F/UTP cable or 100 meters of S/FTP CAT7/Class F cable.

CAT6A is the ANSI/TIA 10-Gigabit Ethernet (10-GbE) over copper standard. Its requirements are covered in ANSI/TIA-568-C.2 (Balanced Twisted-Pair Communications Cabling and Components Standard) published in August 2009. It defines 10-Gigabit data transmission over a 4-connector twisted-pair CAT6A copper cable for a distance of 100 meters.

Category 6A cabling is designed to support next-generation applications, including the transfer of large amounts of data at high speeds, up to 10 Gbps. CAT6A extends electrical specifications to 500 MHz from 250 MHz for CAT6 cabling. CAT6A cables are fully backward compatible with previous categories, including CAT6 and 5e. Category 6A is also designed to support bundled cable installations up to 100 meters and PoE+ low-power implementations. The standard includes the performance parameter, Alien Crosstalk (ANEXT). Because of its higher performance transmission speeds and higher MHz rating, CAT6A cable needs to be tested for external noise outside the cable, which wasn’t a concern with previous cabling categories. CAT6A UTP also has a much larger diameter than previous cables.

Alien crosstalk (ANEXT) is a critical and unique measurement in 10-GbE systems. Crosstalk, measured in 10/100/1000BASE-T systems, is the mixing of signals between wire pairs within a cable. Alien Crosstalk, in 10-GbE systems, is the measurement of the unwanted signal coupling between wire pairs in different and adjacent cables or from one balanced twisted-pair component, channel, or permanent link to another.

The amount of ANEXT depends on a number of factors, including the type of cable, cable jacket, cable length, cable twist density, proximity of adjacent cables, and connectors, and EMI. Patch panels and connecting hardware are also affected by ANEXT.

With Alien Crosstalk, the affected cable is called the victim cable. The surrounding cables are the disturber cables.

There are a number of ways to mitigate the effects of ANEXT in CAT6A runs. According to the standards, ANEXT can be improved by laying CAT6A UTP cable loosely in pathways and raceways with space between the cables. This contrasts to the tightly bundled runs of CAT6/5e cable that we are used to. The tight bundles present a worst-case scenario of six cables around one, thus the center cable would be adversely affected by ANEXT. CAT6A UTP cable needs to be tested for ANEXT. This is a complex and time-consuming process in which all possible wire-pair combinations need to be tested for ANEXT and far-end ANEXT. It can take 50 minutes to test one link in a bundle of 24 CAT 6A UTP cables.

To virtually eliminate the problem of ANEXT, you can use CAT6A F/UTP cable. The F indicates an outer foil shield encasing four unshielded twisted pairs. This cable is also a good choice when security is an issue because it doesn’t emit signals. In addition, CAT6A F/UTP cable works well in noisy environments with a lot of EMI/RFI.

Installation of CAT6A F/UTP is simpler, too, because the cable features a smaller outside diameter than CAT6A UTP. Its construction makes it easier to pull and more resilient. The cable also has a smaller diameter so you can run more cables in a conduit or pathway, and have greater patch panel port density.

For more information, see the CAT6A F/UTP vs. UTP: What You Need to Know white paper in the Resources section at blackbox.com. collapse


Black Box Explains...Category 5, 5e, and 6 copper wiring standards.

The ABCs of standards
There are two primary organizations dedicated to developing and setting structured cabling standards. In North America, standards are issued by the Telecommunications Industry Association (TIA),... more/see it nowwhich is accredited by the American National Standards Institute (ANSI). The TIA was formed in April 1988 after a merger with the Electronics Industry Association (EIA). That’s why its standards are commonly known as ANSI/TIA/EIA, TIA/EIA, or TIA.

Globally, the organizations that issue standards are the International Electrotechnical Commission (IEC) and the International Organization for Standardization (ISO). Standards are often listed as ISO/IEC. Other organizations include the Canadian Standards Association (CSA), CENELEC (European Committee for Electrotechnical Standardizations), and the Japanese Standards Association (JSA/JSI).

The committees of all these organizations work together and the performance requirements of the standards are very similar. But there is some confusion in terminology.

The TIA cabling components (cables, connecting hardware, and patch cords) are labeled with a ”category.” These components together form a permanent link or channel that is also called a ”category.” The ISO/IEC defines the link and channel requirements with a ”class” designation. But the components are called a ”category.”

The Standards
Category 5 (CAT5), ratified in 1991, was the de facto standard for 100-Mbps networks during the 1990s. It is no longer recognized by the TIA/EIA for use in data networking.

Category 5e (CAT5e)–ISO/IEC 11801 Class D, ratified in 1999, is designed to enable twisted-pair cabling to support full-duplex, 4-pair transmission in 100-MHz applications. The CAT5e standard added more headroom and established new requirements to support Gigabit Ethernet over a worst case four-connector channel. These include stricter specs for Near-End Crosstalk (NEXT) and Return Loss (RL). The standard also introduced the required measurements for Power Sum Near-End Crosstalk (PS-NEXT), Equal-Level Far-End Crosstalk (EL-FEXT), and Power Sum Equal-Level Far-End Crosstalk (PS-ELFEXT). CAT5e is still used in many organizations, although it is no longer recognized for new installations.

Category 6 (CAT6)–Class E has a specified frequency of 250 MHz, significantly improved bandwidth capacity over CAT5e, and easily handles Gigabit Ethernet transmissions. In recent years, it has been the cable of choice for new structured cabling systems. CAT6 supports 1000BASE-T and, depending on the installation, 10GBASE-T (10-GbE).

10-GbE over CAT6 introduces the problem of Alien Crosstalk (ANEXT), the unwanted coupling of signals between adjacent pairs and cables. Because ANEXT in CAT6 10-GbE networks is so dependent on installation practices, TSB-155 qualifies 10-GbE over CAT6 up to 55 meters and requires it to be 100% tested. To mitigate ANEXT in CAT6, it is recommended that you unbundle the cables and increase the separation between the cables.

Augmented Category 6 (CAT6a)–Class Ea was ratified in February 2008. This standard calls for 10-Gigabit Ethernet data transmission over a 4-pair copper cabling system up to 100 meters. CAT6a extends CAT6 electrical specifications from 250 MHz to 500 MHz. It introduces the ANEXT requirement. It also replaces the term Equal Level Far-End Crosstalk (ELFEXT) with Attenuation to Crosstalk Ratio, Far-End (ACRF) to mesh with ISO terminology. CAT6a provides improved insertion loss over CAT6. It is a good choice for noisy environments with lots of EMI. CAT6a is also well-suited for use with PoE+.

CAT6a UTP cable is significantly larger than CAT6 cable. It features larger conductors, usually 22 AWG, and is designed with more space between the pairs to minimize ANEXT. The outside diameter of CAT6a cable averages 0.29–0.35" compared to 0.21–0.24" for CAT6 cable. This reduces number of cables you can fit in a conduit. At a 40% fill ratio, you can run three CAT6a cables in a 3/4" conduit vs. five CAT6 cables.

There are two types of CAT6a cable, UTP and F/UTP. For a discussion of the differences, see the white paper in our Resources section.

Category 7 (CAT7)–Class F was published in 2002 by the ISO/IEC. It is not a TIA recognized standard. Class 7 specifies minimum performance standards for fully shielded cable (individually shielded pairs surrounded by an overall shield) transmitting data at rates up to 600 MHz. It offers greater capacity for demanding applications such as broadband video. It’s also well suited for applications where fiber optic cable would typically be used—but it costs less. Because each CAT7 pair is fully shielded, it's ideal for areas prone to EMI/RFI. Class 7 cable offers two connector styles: the standard RJ plug and a non-RJ-style plug and socket interface specified in IEC 61076-2-104:2.

Category 7a (CAT7a)–Class Fa is currently in ISO standards for channel performance in Amendment 1, recently component performance has been ratified in Amendment 2. The formal names are ISO 11801 Amendment 1 (2008) and ISO 11801 Amendment 2 (2010). Class Fa cable is a fully shielded cable that extends frequency from 600 MHz to 1000 MHz. It can easily handle 10-GbE and offers users a lifespan of 15 years or more. It has even been discussed that Class Fa cable is the future for 40GBASE-T or more.


For a comparison chart of category performance standards, see the Buyer's Guide in the Resources section.
collapse


Black Box Explains...Category 6.

Category 6 (CAT6)–Class E has a specified frequency of 250 MHz, significantly improved bandwidth capacity over CAT5e, and easily handles Gigabit Ethernet transmissions. In recent years, it has been the... more/see it nowcable of choice for new structured cabling systems. CAT6 supports 1000BASE-T and, depending on the installation, 10GBASE-T (10-GbE).

10-GbE over CAT6 introduces the problem of Alien Crosstalk (ANEXT), the unwanted coupling of signals between adjacent pairs and cables. Because ANEXT in CAT6 10-GbE networks is so dependent on installation practices, TSB-155 qualifies 10-GbE over CAT6 up to 55 meters and requires it to be 100% tested. To mitigate ANEXT in CAT6, it is recommended that you unbundle the cables and increase the separation between the cables.

You can always contact Black Box Tech Support to answer your cabling questions. Our techs can recommend cable testers and steer you in the right direction when you’re installing new cabling. And the advice is FREE! collapse


Black Box Explains...Shielded vs. unshielded cable.

The environment determines whether cable should be shielded or unshielded.

Shielding is the sheath surrounding and protecting the cable wires from electromagnetic leakage and interference. Sources of this electromagnetic activity... more/see it now(EMI)—commonly referred to as noise—include elevator motors, fluorescent lights, generators, air conditioners, and photocopiers. To protect data in areas with high EMI, choose a shielded cable.

Foil is the most basic cable shield, but a copper-braid shield provides more protection. Shielding also protects cables from rodent damage. Use a foil-shielded cable in busy office or retail environments. For industrial environments, you might want to choose a copper-braid shield.

For quiet office environments, choose unshielded cable. collapse


Black Box Explains…CAT6A UTP vs. F/UTP.

CAT6A is currently the cable of choice for future-proofing cabling installations and for 10-GbE networks.

There are two types of CAT6A cable, unshielded (UTP) and shielded (F/UTP). F/UTP denotes foiled/unshielded... more/see it nowtwisted pair and consists of four unshielded twisted pairs encased in an overall foil shield. This is not to be confused with an S/FTP (screened/foiled twisted pair) cable, which has four individually shielded twisted pairs encased in an overall braided shield.

CAT6A UTP
CAT6A UTP is constructed in a certain way to help eliminate crosstalk and ANEXT. (ANEXT is the measurement of the signal coupling between wire pairs in different and adjacent cables.) This includes larger conductors (23 AWG minimum), tighter twists, an extra internal airspace, an internal separator between the pairs, and a thicker outer jacket. These features also increase the outer diameter of the cable, typically to .35 inches in diameter, up from .25 inches for CAT6 cable. This increased diameter creates a greater distance between pairs in adjacent links, thus reducing the between-channel signal coupling. But CAT6A UTP cable is still affected by ANEXT.

According to the standards, ANEXT can be improved by laying CAT6A UTP cable loosely in pathways and raceways with space between the cables. This contrasts to the tightly bundled runs of CAT6/5e cable we are used to. The tight bundles present a worst-case scenario of six cables around one, thus the center cable would be adversely affected by ANEXT. Testing for ANEXT is a complex and time-consuming process where all possible wire-pair combinations are checked. It can take up to 50 minutes to test one link in a bundle of 24 CAT6A UTP cables.

CAT6A F/UTP
CAT6A F/UTP denotes foiled/unshielded twisted pairs and consists of four unshielded twisted pairs encased in an overall foil shield. ANEXT, and the time needed to test for it, can be greatly reduced, if not eliminated completely, by using CAT6A F/UTP. The foil shield acts as a barrier preventing external EMI/RFI from coupling onto the twisted pairs. It also prevents data signals from leaking out of the cable, making the cable more difficult to tap and better for secure installations. Studies also have shown that CAT6A F/UTP cable provides significantly more headroom (as much as 20 dB) than CAT6A UTP in 10-GbE over copper systems.

Bigger isn't always better.
CAT6A UTP cable has an overall allowable diameter of 0.354 inches. CAT6A F/UTP cable has an average outside diameter of 0.265–0.30 inches. That’s smaller than the smallest CAT6A UTP cable. An increase in the outside diameter (O.D.) of 0.1 inch, from 0.25 inches to 0.35 inches for example, represents a 21% increase in fill volume. In general, CAT6A F/UTP cable provides a minimum of 35% more fill capacity that CAT6A UTP cable.

Also because of its large diameter, CAT6A UTP requires a larger bend radius, more pathways, less dense patch panel connections, and extensive ANEXT testing.

CAT6A F/UTP cable is actually easier to handle, requires less bend radius, and uses smaller pathways. In addition, innovations in connector technology has made terminating CAT6A F/UTP cable simpler. In terms of grounding, the requirements for both UTP and F/UTP cable fall under TIA/EIA J-STD-607-A Commercial Building Grounding (Earthing) and Bonding Requirements for Telecommunications.

The advantages of CAT6A F/UTP vs. UTP
In summary, there are a number of advantages of using CAT6A F/UTP over CAT6A UTP in 10-GbE networks.

1. Shielding eliminates ANEXT and EMI/RFI problems and testing.
2. Data line security is enhanced because of shielding.
3. Lighter, slimmer cable provides higher port density.
4. Smaller outside diameter cable is easier to handle and reduces installation costs.
5. Shielded cable uses less space in conduits.

For more information, see the CAT6A F/UTP vs. UTP: What You Need to Know white paper in the Resources section at blackbox.com. collapse


Black Box Explains...Straight-pinned and crossover cable.

Straight-pinned cable has the most common type of pinning. The send and receive pairs are wired straight-through on either end of the cable.

Crossover cable is generally used for peer-to-peer connections.... more/see it nowThe send and receive pairs are crossed between Connector A to Connector B on either end of the cable. collapse


Black Box Explains...Augmented Category 6 (CAT6A).


CAT6A is a 10-Gigabit Ethernet over copper proposal to the CAT6 standard. The IEEE published a draft standard (Std 802.3an) in October 2004.

The draft calls for 10-Gigabit data transmission... more/see it nowover a 4-pair twisted-pair copper cable for a distance of 100 meters on Class F or Class E-augmented copper cabling.

Class E cabling requires a line-encoding scheme (PAM 12) and electronics to achieve the 10-Gbps transmission for 100 meters. Current CAT6 cabling systems may support 10-Gigabit Ethernet over limited distances.

The draft extends CAT6 electrical specifications from 250 MHz to 500 MHz. It also proposes a new measurement: Power-Sum Alien Crosstalk to 500 MHz. Alien Crosstalk is a coupled signal in a disturbed pair arising from a signal in a neighboring cable. collapse


Black Box Explains...Cable termination.


Carefully remove the jacketing from the cable and expose one inch of the insulated wire conductors. Do not remove any insulation from the conductors. When the... more/see it nowRJ-45 connector is crimped, the contacts inside will pierce the conductor insulation.


Untwist the wires to within 1/8" of the jacket. Arrange the wires according to the cable spec (568B in this case). Flatten and align the wires. Make one straight cut across all the conductors, removing approximately 1/2" to ensure the ends are of equal length.


Slide the wires into a connector. The cable jacket should extend into the connector about 1/4" for strain relief. Orient the wires so connector Pin 1 aligns with cable Pin 1, etc. Hold the connector in front of you. With the locking tab down, Pin 1 is on the far left.


Insert the connector into a crimp tool. Make sure you’re using the proper die. Firmly squeeze the handles. They’ll lock in a ratcheting action. A final click indicates the connector is firmly latched.


Check your work using a continuity tester or cable certifier rated for the cable standard you’re installing. Your tester should be able to check for shorts, opens, or miswires.


collapse


Black Box Explains...Category 3 and 4

Category 3 is the performance level for voice and data transmission up to 16 MHz or 10 Mbps, such as 4-Mbps Token Ring and 10BASE-T.

Category 4 is the... more/see it nowperformance level for voice and data transmission up to 20 MHz or 16 Mbps, such as 4-/16-Mbps UTP.

Both offer solid performance, and Black Box guarantees their reliability. But if you think you may be upgrading your network within the next few years, consider Category 5 cable. It offers more speed and versatility than Category 3 or 4 at a minimal cost difference. collapse


Black Box Explains...Solid vs. stranded cable.

Solid-conductor cable is designed for backbone and horizontal cable runs. Use it for runs between two wiring closets or from the wiring closet to a wallplate. Solid cable shouldn’t be... more/see it nowbent, flexed, or twisted repeatedly. Its attenuation is lower than that of stranded-conductor cable.

Stranded cable is for use in shorter runs between network interface cards (NICs) and wallplates or between concentrators and patch panels, hubs, and other rackmounted equipment. Stranded-conductor cable is much more flexible than solid-core cable. However, attenuation is higher in stranded-conductor cable, so the total length of stranded cable in your system should be kept to a minimum to reduce signal degradation. collapse